Includes these tests from MIL STD 704F:

HDC101 Load Measurements - 270 V DC
HDC102 - A Nominal (270 V DC)
HDC102 - B NLSS (250 V DC)
HDC102 - C NHSS (280 V DC)
HDC103 Template
HDC105 (270 VDC) - Repetitive Transient
AA (280 VDC) - Overvoltage Transient (330 VDC)
BB (280 VDC) - Overvoltage Transient (330 VDC)
CC (280 VDC) - Overvoltage Transient (305 VDC)
DD (280 VDC) - Overvoltage Transient (305 VDC)
EE (280 VDC) - Overvoltage Transient x3 (330 VDC)
FF (250 VDC) - Overvoltage Transient (330 VDC)
GG (250 VDC) - Overvoltage Transient (330 VDC)
HH (250 VDC) - Overvoltage Transient (305 VDC)
II (250 VDC) - vervoltage Transient (305 VDC)
JJ (250 VDC) - Overvoltage Transient x3 (330 VDC)
KK (280 VDC) - Undervoltage Transient (200 VDC)
LL (280 VDC) - Undervoltage Transient (200 VDC)
MM (280 VDC) - Undervoltage Transient x3 (200 VDC)
NN (250 VDC) - Undervoltage Transient (200 VDC)
OO (250 VDC) - Undervoltage Transient (200 VDC)
PP (250 VDC) - Undervoltage Transient x3 (200 VDC)
QQ (280 VDC) - Combined Transient (200-330 VDC)
RR (250 VDC) - Combined Transient (200-330 VDC)
HDC201 A (270V) - Transfer Interrupt - Nominal Voltage (50 ms)
B (250V) - Transfer Interrupt - NLSS Voltage (50 ms)
C (280V) - Transfer Interrupt - NHSS Voltage (50 ms)
D (270V) - Transfer Interrupt - Nominal Voltage (30 ms)
E (250V) - Transfer Interrupt - NLSS Voltage (30 ms)
F (280V) - Transfer Interrupt - NHSS Voltage (30 ms)
G (270V) - Transfer Interrupt - Nominal Voltage (10 ms)
H (250V) - Transfer Interrupt - NLSS Voltage (10 ms)
I (280V) - Transfer Interrupt - NHSS Voltage (10 ms)
J (270V) - Transfer Interrupt x3 - Nominal Voltage
K (270V) - Transfer Interrupt - Overvoltage (330 VDC)
L (270V) - Transfer Interrupt - Undervoltage (200 VDC)
HDC301 A (270 V DC) - Undervoltage Transients (240 V DC)
B (270 V DC) - Overvoltage Transients (290 V DC)
HDC302 AA (280 V DC) - Overvoltage Transients (350 V DC)
BB (280 V DC) - Overvoltage Transients (350 V DC)
CC (280 V DC) - Overvoltage Transients x3 (350 V DC)
DD (250 V DC) - Overvoltage Transients (350 V DC)
EE (250 V DC) - Overvoltage Transients (350 V DC)
FF (250 V DC) - Overvoltage Transients x3 (350 V DC)
GG (280 V DC) - Undervoltage Transients (180 V DC)
HH (280 V DC) - Undervoltage Transients (180 V DC)
II (280 V DC) - Undervoltage Transients x3 (180 V DC)
JJ (250 V DC) - Undervoltage Transients (180 V DC)
KK (250 V DC) - Undervoltage Transients (180 V DC)
LL (250 V DC) - Undervoltage Transients x3 (180 V DC)
MM (280 V DC) - Combined Transients (180-350 V DC)
HDC401 A (270 V DC) - Steady State Limits for Voltage (250 V DC)
A (704B,C,D) (270 V DC) - Steady State Limits for Voltage (240 V DC)
B (270 V DC) - Steady State Limits for Voltage (280 V DC)
B (704B,C,D) (270 V DC) - Steady State Limits for Voltage (290 V DC)
HDC501 A (704B,C) (270 V DC) - Starting Voltage Transients (155 V DC)
AA (270 V DC) - Starting Voltage Transients (115 V DC)
HDC601 A (270 V DC) - Power Failures (100 ms)
B (270 V DC) - Power Failures (500 ms)
C (270 V DC) - Power Failures (3000 ms)
D (270 V DC) - Power Failures (7000 ms)
HDC602 Correct Phase Connection (270 V DC)
  Phase Reversal (270 V DC)
LDC101 Load Measurements - 28 V DC
LDC102 A - Nominal (28 V DC)
B - NLSS (22 V DC)
C - NLSS (29 V DC)
LDC103 Template
LDC105 (28.5 VDC) - Repetitive Transient
AA (29 VDC) - Overvoltage Transient (50 VDC)
BB (29 VDC) - Overvoltage Transient (50 VDC)
CC (29 VDC) - Overvoltage Transient (40 VDC)
DD (29 VDC) - Overvoltage Transient (40 VDC)
EE (29 VDC) - Overvoltage Transient x 3 (50 VDC)
FF (22 VDC) - Overvoltage Transient (50 VDC)
GG (22 VDC) - Overvoltage Transient (50 VDC)
HH (22 VDC) - Overvoltage Transient (40 VDC)
II (22 VDC) - Overvoltage Transient (40 VDC)
JJ (22 VDC) - Overvoltage Transient x 3 (50 VDC)
KK (29 VDC) - Undervoltage Transient (18 VDC)
LL (29 VDC) - Undervoltage Transient (18 VDC)
MM (29 VDC) - Undervoltage Transient x3 (18 VDC)
NN (22 VDC) - Undervoltage Transient (18 VDC)
OO (22 VDC) - Undervoltage Transient (18 VDC)
PP (22 VDC) - Undervoltage Transient x3 (18 VDC)
QQ (29 VDC) - Combined Transient (18-50 VDC)
RR (22 VDC) - Combined Transient (18-50 VDC)
LDC201 A (28V) - Transfer Interrupt - Nominal Voltage (50 ms)
B (22V) - Transfer Interrupt - NLSS Voltage (50 ms)
C (29V) - Transfer Interrupt - NHSS Voltage (50 ms)
D (28V) - Transfer Interrupt - Nominal Voltage (30 ms)
E (22V) - Transfer Interrupt - NLSS Voltage (30 ms)
F (29V) - Transfer Interrupt - NHSS Voltage (30 ms)
G (28V) - Transfer Interrupt - Nominal Voltage (10 ms)
H (22V) - Transfer Interrupt - NLSS Voltage (10 ms)  
I (29V) - Transfer Interrupt - NHSS Voltage (10 ms)
J (28V) - Transfer Interrupt x3 - Nominal Voltage
K (28V) - Transfer Interrupt - Overvoltage (50 VDC)
L (28V) - Transfer Interrupt - Undervoltage (18 VDC)
LDC301 A (28 V DC) - Undervoltage Transients (20 V DC)
B (28 V DC) - Overvoltage Transients (31,5 V DC)
LDC302 AAA (29 V DC) - Overvoltage Transients (50 V DC)
BBB (29 V DC) - Overvoltage Transients (50 V DC)
CCC (29 V DC) - Overvoltage Transients x3 (50 V DC)
DDD (22 V DC) - Overvoltage Transients (50 V DC)
EEE (22 V DC) - Overvoltage Transients (50 V DC)
FFF (22 V DC) - Overvoltage Transients x3 (50 V DC)
GGG (29 V DC) - Undervoltage Transients (7 V DC)
HHH (29 V DC) - Undervoltage Transients (7 V DC)
III (29 V DC) - Undervoltage Transients x3 (7 V DC)
JJJ (22 V DC) - Undervoltage Transients (7 V DC)
KKK (22 V DC) - Undervoltage Transients (7 V DC)
LLL (22 V DC) - Undervoltage Transients x3 (7 V DC)
MMM (29 V DC) - Combined Transients (7-50 V DC)
NNN (22 V DC) - Combined Transients (7-50 V DC)
Template for A-V (704A) and AA-NN (704B-704D)
LDC401 A (28 V DC) - Steady State Limits for Voltage (18 V DC)
A (704A,C,D) (28 V DC) - Steady State Limits for Voltage (16 V DC)
A (704B) (28 V DC) - Steady State Limits for Voltage (18 V DC) 
B (28 V DC) - Steady State Limits for Voltage (29 V DC)
B (704B) (28 V DC) - Steady State Limits for Voltage (29 V DC)
B (704C) (28 V DC) - Steady State Limits for Voltage (30 V DC)
B (704D) (28 V DC) - Steady State Limits for Voltage (29 V DC)
LDC501 A (704A,B,C) (28,5 V DC) - Starting Voltage Transients (16 V DC)
AA (29 V DC) - Starting Voltage Transients (12 V DC)
LDC601 A (28 V DC)- Power Failures (100 ms)
B (28 V DC)- Power Failures (500 ms)
C (28 V DC)- Power Failures (3000 ms)
D (28 V DC)- Power Failures (7000 ms)
LDC602 Correct Phase Connection (28 V DC)
  Phase Reversal (28 V DC)
SAC101 Load Measurements - 115 V, 400Hz
SAC102 A - Nominal Voltage, Nominal Frequency
B - Nominal Voltage, NLSS Frequency
C - Nominal Voltage, NHSS Frequency
D - NLSS Voltage, Nominal Frequency
E - NLSS Voltage, NLSS Frequency
F - NLSS Voltage, NHSS Frequency
G - NHSS Voltage, Nominal Frequency
H - NHSS Voltage, NLSS Frequency
I - NHSS Voltage, NHSS Frequency
SAC105 A - 1Hz per second
B - 5Hz per second
C - 10Hz per second
D - 25Hz per second
E - 100Hz per second
SAC106 (Ripple)  A - 316 mVrms with 50 Hz Voltage Distortion
B - 316 mVrms with 100 Hz Voltage Distortion
C - 1580 mVrms with 500 Hz Voltage Distortion
D - 3160 mVrms with 1 kHz Voltage Distortion
E - 3160 mVrms with 2 kHz Voltage Distortion
F - 3160 mVrms with 3 kHz Voltage Distortion
G - 1900 mVrms with 5 kHz Voltage Distortion
H - 950 mVrms with 10 kHz Voltage Distortion
SAC108 A - 115 Vrms with +100 mV DC offset
  B - 115 Vrms with -100 mV DC offset
SAC109  (MIL-STD-704A version) Test Conditions A-O Template
  AA - Overvoltage Transients (140 Vrms)
  A-O Template (for MIL-STD-704A version)
  BB - Overvoltage Transients (140 Vrms)
  CC - Overvoltage Transients (160 Vrms)
  DD - Overvoltage Transients (160 Vrms)
  EE - Overvoltage Transients (180 Vrms)
  FF - Overvoltage Transients (180 Vrms)
  GG - Overvoltage Transients x3 (180 Vrms)
  HH - Undervoltage Transients (90 Vrms)
  II - Undervoltage Transients (90 Vrms)
  JJ - Undervoltage Transients (80 Vrms)
  KK - Undervoltage Transients (80 Vrms)
  LL - Undervoltage Transients x3 (80 Vrms)
  MM - Combined Transients (80-180 Vrms)
  Repetitive Normal Voltage Transients
SAC110 (MIL-STD-704A version) Test Conditions A-I Template
  AA - Overfrequency Transients (410 Hz)
  BB - Overfrequency Transients (420 Hz)
  CC - Overfrequency Transients (425 Hz)
  DD - Overfrequency Transients (425-410 Hz)
  EE - Underfrequency Transients (390 Hz)
  FF - Underfrequency Transients (380 Hz)
  GG - Underfrequency Transients (375 Hz)
  HH - Underfrequency Transients (375-390 Hz)
  II - Combined Frequency Transients (375-425 Hz)
SAC201 A - Transfer Interrupt - Nominal Voltage (50 ms)
  B - Transfer Interrupt - NLSS Voltage (50 ms)
  C - Transfer Interrupt - NHSS Voltage (50 ms)
  D - Transfer Interrupt - Nominal Voltage (30 ms)
  E - Transfer Interrupt - NLSS Voltage (30 ms)
  F - Transfer Interrupt - NHSS Voltage (30 ms)
  G - Transfer Interrupt - Nominal Voltage (10 ms)
  H - Transfer Interrupt - NLSS Voltage (10 ms)
  I - Transfer Interrupt - NHSS Voltage (10 ms)
  J - Transfer Interrupt x3 - Nominal Voltage (50 ms)
  K - Transfer Interrupt - Nominal Voltage + Overvoltage
  L - Transfer Interrupt - Nominal Voltage + Undervoltage
SAC301 A - Abnormal Steady State Limits (115 Vrms, 380 Hz)
  B - Abnormal Steady State Limits (115 Vrms, 420 Hz)
  C - Abnormal Steady State Limits (100 Vrms, 400 Hz)
  D - Abnormal Steady State Limits (100 Vrms, 380 Hz)
  E - Abnormal Steady State Limits (100 Vrms, 420 Hz)
  F - Abnormal Steady State Limits (125 Vrms, 400 Hz)
  G - Abnormal Steady State Limits (125 Vrms, 380 Hz)
  H - Abnormal Steady State Limits (125 Vrms, 420 Hz)
SAC302 A (704A only) - Overvoltage Transients (140 Vrms)
  AA - Overvoltage Transients (140 Vrms)
  B (704A only) - Overvoltage Transients (140 Vrms)
  BB - Overvoltage Transients (140 Vrms)
  C (704A only) - Overvoltage Transients (160 Vrms)
  CC - Overvoltage Transients (160 Vrms)
  D (704A only) - Overvoltage Transients (160 Vrms)
  DD - Overvoltage Transients (160 Vrms)
  E (704A only) - Overvoltage Transients (180 Vrms)
  EE - Overvoltage Transients (180 Vrms)
  F (704A only) - Overvoltage Transients (180 Vrms)
  FF - Overvoltage Transients (180 Vrms)
  G (704A only) - Overvoltage Transients x3 (180 Vrms)
  GG - Overvoltage Transients x3 (180 Vrms)
  H (704A only) - Undervoltage Transients (85 Vrms)
  HH - Undervoltage Transients (85 Vrms)
  I (704A only) - Undervoltage Transients (85 Vrms)
  II - Undervoltage Transients (85 Vrms)
  J (704A only) - Undervoltage Transients (75 Vrms)
  JJ - Undervoltage Transients (66 Vrms)
  K (704A only) - Undervoltage Transients (75 Vrms)
  KK - Undervoltage Transients (65 Vrms)
  L (704A only) - Undervoltage Transients (45 Vrms)
  LL - Undervoltage Transients (45 Vrms)
  M (704A only) - Undervoltage Transients (45 Vrms)
  MM - Undervoltage Transients (45 Vrms)
  N (704A only) - Undervoltage Transients x3 (45 Vrms)
  NN - Undervoltage Transients x3 (45 Vrms)
  O (704A only) - Combined Transients (45-180 Vrms)
  OO - Combined Transients (180 Vrms)
SAC303 A (704A) - Overfrequency Transients (480 Hz)
  AA - Overfrequency Transients (480 Hz)
  B (704A) - Overfrequency Transients (480 Hz)
  BB - Overfrequency Transients (480 Hz)
  C (704A) - Underfrequency Transients (320 Hz)
  CC - Underfrequency Transients (320 Hz)
  D (704A) - Underfrequency Transients (320 Hz)
  DD - Underfrequency Transients (320 Hz)
  E (704A) - Combined Transients (320-480 Hz)
  EE - Combined Transients (320-480 Hz)
SAC401 A - Emergency Steady State Limits - 115 V, 393 Hz
  A (704A-D) - Emergency Steady State Limits - 115 V, 360 Hz
  B - Emergency Steady State Limits - 115 V, 407 Hz
  B (704A-D) - Emergency Steady State Limits - 115 V, 440 Hz
  C - Emergency Steady State Limits - 104 V, 400 Hz
  C (704A,C,D) - Emergency Steady State Limits - 104 V, 400 Hz
  C (704B) - Emergency Steady State Limits - 102 V, 400 Hz
  D - Emergency Steady State Limits - 104 V, 393 Hz
  D (704A,C,D) - Emergency Steady State Limits - 104 V, 360 Hz
  D (704B) - Emergency Steady State Limits - 102 V, 360 Hz
  E - Emergency Steady State Limits - 104 V, 407 Hz
  E (704A,C,D) - Emergency Steady State Limits - 104 V, 440 Hz
  E (704B) - Emergency Steady State Limits - 102 V, 440 Hz
  F - Emergency Steady State Limits - 118 V, 400 Hz
  F (704A,C,D) - Emergency Steady State Limits - 122 V, 400 Hz
  F (704B) - Emergency Steady State Limits - 124 V, 400 Hz
  G - Emergency Steady State Limits - 118 V, 393 Hz
  G (704A,C,D) - Emergency Steady State Limits - 122 V, 360 Hz
  G (704B) - Emergency Steady State Limits - 124 V, 360 Hz
  H - Emergency Steady State Limits - 118 V, 407 Hz
  H (704A,C,D) - Emergency Steady State Limits - 122 V, 440 Hz
  H (704B) - Emergency Steady State Limits - 124 V, 440 Hz
SAC601 A - Power Failures (100 ms)
  B - Power Failures (500 ms)
  C - Power Failures (3000 ms)
  D - Power Failures (7000 ms)
SAC603 Correct Phase Connection
  Phase Reversal
SVF101 Load Measurements - 115 V, 360Hz
  Load Measurements - 115 V, 400Hz
  Load Measurements - 115 V, 600Hz
  Load Measurements - 115 V, 800Hz
SVF102 Template
SVF105 A (362 Hz) - 1Hz per second
  A (400 Hz) - 1Hz per second
  A (600 Hz) - 1Hz per second
  A (798 Hz) - 1Hz per second
  B (362 Hz) - 5Hz per second
  B (400 Hz) - 5Hz per second
  B (600 Hz) - 5Hz per second
  B (798 Hz) - 5Hz per second
  C (362 Hz) - 10Hz per second
  C (400 Hz) - 10Hz per second
  C (600 Hz) - 10Hz per second
  C (798 Hz) - 10Hz per second
  D (362 Hz) - 25Hz per second
  D (400 Hz) - 25Hz per second
  D (600 Hz) - 25Hz per second
  D (798 Hz) - 25Hz per second
  E (362 Hz) - 100Hz per second
  E (400 Hz) - 100Hz per second
  E (600 Hz) - 100Hz per second
  E (798 Hz) - 100Hz per second
SVF106 (Ripple) A - 316 mVrms with 50 Hz Voltage Distortion
  B - 316 mVrms with 100 Hz Voltage Distortion
  C - 1580 mVrms with 500 Hz Voltage Distortion
  D - 3160 mVrms with 1 kHz Voltage Distortion
  E - 3160 mVrms with 2 kHz Voltage Distortion
  F - 3160 mVrms with 3 kHz Voltage Distortion
  G - 1900 mVrms with 5 kHz Voltage Distortion
  H - 950 mVrms with 10 kHz Voltage Distortion
SVF108 A (360 Hz) - 115 Vrms with +100 mV DC offset
  A (400 Hz) - 115 Vrms with +100 mV DC offset
  A (600 Hz) - 115 Vrms with +100 mV DC offset
  A (800 Hz) - 115 Vrms with +100 mV DC offset
  B (360 Hz) - 115 Vrms with -100 mV DC offset
  B (400 Hz) - 115 Vrms with -100 mV DC offset
  B (600 Hz) - 115 Vrms with -100 mV DC offset
  B (800 Hz) - 115 Vrms with -100 mV DC offset 
 SVF109 A (360 Hz) - Overvoltage Transients (140 Vrms)
  A (400 Hz) - Overvoltage Transients (140 Vrms)
  A (600 Hz) - Overvoltage Transients (140 Vrms)
  A (800 Hz) - Overvoltage Transients (140 Vrms)
  B (360 Hz) - Overvoltage Transients (140 Vrms)
  B (400 Hz) - Overvoltage Transients (140 Vrms)
  B (600 Hz) - Overvoltage Transients (140 Vrms)
  B (800 Hz) - Overvoltage Transients (140 Vrms)
  C (360 Hz) - Overvoltage Transients (160 Vrms)
  C (400 Hz) - Overvoltage Transients (160 Vrms)
  C (600 Hz) - Overvoltage Transients (160 Vrms)
  C (800 Hz) - Overvoltage Transients (160 Vrms)
  D (360 Hz) - Overvoltage Transients (160 Vrms)
  D (400 Hz) - Overvoltage Transients (160 Vrms)
  D (600 Hz) - Overvoltage Transients (160 Vrms)
  D (800 Hz) - Overvoltage Transients (160 Vrms)
  E (360 Hz) - Overvoltage Transients (180 Vrms)
  E (400 Hz) - Overvoltage Transients (180 Vrms)
  E (600 Hz) - Overvoltage Transients (180 Vrms)
  E (800 Hz) - Overvoltage Transients (180 Vrms)
  F (360 Hz) - Overvoltage Transients (180 Vrms)
  F (400 Hz) - Overvoltage Transients (180 Vrms)
  F (600 Hz) - Overvoltage Transients (180 Vrms)
  F (800 Hz) - Overvoltage Transients (180 Vrms)
  G (360 Hz) - Overvoltage Transients x3 (180 Vrms)
  G (400 Hz) - Overvoltage Transients x3 (180 Vrms)
  G (600 Hz) - Overvoltage Transients x3 (180 Vrms)
  G (800 Hz) - Overvoltage Transients x3 (180 Vrms)
  H (360 Hz) - Undervoltage Transients (90 Vrms)
  H (400 Hz) - Undervoltage Transients (90 Vrms) 
  H (600 Hz) - Undervoltage Transients (90 Vrms)
  H (800 Hz) - Undervoltage Transients (90 Vrms)
  I (360 Hz) - Undervoltage Transients (90 Vrms)
  I (400 Hz) - Undervoltage Transients (90 Vrms)
  I (600 Hz) - Undervoltage Transients (90 Vrms)
  I (800 Hz) - Undervoltage Transients (90 Vrms)
  J (360 Hz) - Undervoltage Transients (80 Vrms)
  J (400 Hz) - Undervoltage Transients (80 Vrms)
  J (600 Hz) - Undervoltage Transients (80 Vrms)
  J (800 Hz) - Undervoltage Transients (80 Vrms)
  K (360 Hz) - Undervoltage Transients (80 Vrms)
  K (400 Hz) - Undervoltage Transients (80 Vrms)
  K (600 Hz) - Undervoltage Transients (80 Vrms)
  K (800 Hz) - Undervoltage Transients (80 Vrms)
  L (360 Hz) - Undervoltage Transients x3 (80 Vrms)
  L (400 Hz) - Undervoltage Transients x3 (80 Vrms)
  L (600 Hz) - Undervoltage Transients x3 (80 Vrms)
  L (800 Hz) - Undervoltage Transients x3 (80 Vrms)
  M (360 Hz) - Combined Transients (80-180 Vrms)
  M (400 Hz) - Combined Transients (80-180 Vrms)
  M (600 Hz) - Combined Transients (80-180 Vrms)
  M (800 Hz) - Combined Transients (80-180 Vrms) 
  Repetitive Normal Voltage Transients (360 Hz) 
  Repetitive Normal Voltage Transients (400 Hz)
  Repetitive Normal Voltage Transients (600 Hz)
  Repetitive Normal Voltage Transients (800 Hz)
 SVF110 A - Overfrequency Transients (360-800 Hz)
  B - Overfrequency Transients (360-800 Hz)
  C - Overfrequency Transients (360-600 Hz)
  D - Overfrequency Transients (360-600 Hz)
  E - Underfrequency Transients (800-360 Hz)
  F - Underfrequency Transients (800-360 Hz)
  G - Underfrequency Transients (800-600 Hz)
  H - Underfrequency Transients (800-600 Hz)
  I - Combined Frequency Transients (800-360 Hz)
 SVF201 A (360 Hz) - Transfer Interrupt - Nominal Voltage (50 ms)
  A (400 Hz) - Transfer Interrupt - Nominal Voltage (50 ms)
  A (600 Hz) - Transfer Interrupt - Nominal Voltage (50 ms)
  A (800 Hz) - Transfer Interrupt - Nominal Voltage (50 ms)
  B (360 Hz) - Transfer Interrupt - NLSS Voltage (50 ms)
  B (400 Hz) - Transfer Interrupt - NLSS Voltage (50 ms)
  B (600 Hz) - Transfer Interrupt - NLSS Voltage (50 ms)
  B (800 Hz) - Transfer Interrupt - NLSS Voltage (50 ms)
  C (360 Hz) - Transfer Interrupt - NHSS Voltage (50 ms)
  C (400 Hz) - Transfer Interrupt - NHSS Voltage (50 ms)
  C (600 Hz) - Transfer Interrupt - NHSS Voltage (50 ms)
  C (800 Hz) - Transfer Interrupt - NHSS Voltage (50 ms)
  D (360 Hz) - Transfer Interrupt - Nominal Voltage (30 ms)
  D (400 Hz) - Transfer Interrupt - Nominal Voltage (30 ms)
  D (600 Hz) - Transfer Interrupt - Nominal Voltage (30 ms)
  D (800 Hz) - Transfer Interrupt - Nominal Voltage (30 ms) 
  E (360 Hz) - Transfer Interrupt - NLSS Voltage (30 ms)
  E (400 Hz) - Transfer Interrupt - NLSS Voltage (30 ms)
  E (600 Hz) - Transfer Interrupt - NLSS Voltage (30 ms)
  E (800 Hz) - Transfer Interrupt - NLSS Voltage (30 ms)
  F (360 Hz) - Transfer Interrupt - NHSS Voltage (30 ms)
  F (400 Hz) - Transfer Interrupt - NHSS Voltage (30 ms)
  F (600 Hz) - Transfer Interrupt - NHSS Voltage (30 ms)
  F (800 Hz) - Transfer Interrupt - NHSS Voltage (30 ms)
  G (360 Hz) - Transfer Interrupt - Nominal Voltage (10 ms)
  G (400 Hz) - Transfer Interrupt - Nominal Voltage (10 ms)
  G (600 Hz) - Transfer Interrupt - Nominal Voltage (10 ms)
  G (800 Hz) - Transfer Interrupt - Nominal Voltage (10 ms)
  H (360 Hz) - Transfer Interrupt - NLSS Voltage (10 ms)
  H (400 Hz) - Transfer Interrupt - NLSS Voltage (10 ms)
  H (600 Hz) - Transfer Interrupt - NLSS Voltage (10 ms)
  H (800 Hz) - Transfer Interrupt - NLSS Voltage (10 ms)
  I (360 Hz) - Transfer Interrupt - NHSS Voltage (10 ms)
  I (400 Hz) - Transfer Interrupt - NHSS Voltage (10 ms)
  I (600 Hz) - Transfer Interrupt - NHSS Voltage (10 ms)
  I (800 Hz) - Transfer Interrupt - NHSS Voltage (10 ms)
  J (360 Hz) - Transfer Interrupt x3 - Nominal Voltage
  J (400 Hz) - Transfer Interrupt x3 - Nominal Voltage
  J (600 Hz) - Transfer Interrupt x3 - Nominal Voltage
  J (800 Hz) - Transfer Interrupt x3 - Nominal Voltage
  K (360 Hz) - Transfer Interrupt - Overvoltage
  K (400 Hz) - Transfer Interrupt - Overvoltage
  K (600 Hz) - Transfer Interrupt - Overvoltage
  K (800 Hz) - Transfer Interrupt - Overvoltage
  L (360 Hz) - Transfer Interrupt - Undervoltage
  L (400 Hz) - Transfer Interrupt - Undervoltage
  L (600 Hz) - Transfer Interrupt - Undervoltage
  L (800 Hz) - Transfer Interrupt - Undervoltage
 SVF301 A - Abnormal Steady State Limits (100 Vrms, 400 Hz)
  B - Abnormal Steady State Limits (100 Vrms, 360 Hz)
  C - Abnormal Steady State Limits (100 Vrms, 600 Hz)
  D - Abnormal Steady State Limits (100 Vrms, 800 Hz)
  E - Abnormal Steady State Limits (125 Vrms, 400 Hz)
  F - Abnormal Steady State Limits (125 Vrms, 360 Hz)
  G - Abnormal Steady State Limits (125 Vrms, 600 Hz)
  H - Abnormal Steady State Limits (125 Vrms, 800 Hz)
 SVF302 Abnormal Transients Template (360 Hz)
  Abnormal Transients Template (400 Hz)
  Abnormal Transients Template (600 Hz)
  Abnormal Transients Template (800 Hz)
 SVF303 A (360 Hz) - Overfrequency Transients (800 Hz)
  B (360 Hz) - Overfrequency Transients (800 Hz)
  C (360 Hz) - Overfrequency Transients (600 Hz)
  D (360 Hz) - Overfrequency Transients (600 Hz)
  E (800 Hz) - Underfrequency Transients (360 Hz)
  F (800 Hz) - Underfrequency Transients (360 Hz)
  G (800 Hz) - Underfrequency Transients (600 Hz)
  H (800 Hz) - Underfrequency Transients (600 Hz)
  I (600 Hz) - Combined Transients (360-800 Hz)
 SVF401 Template
 SVF601 A (360 Hz) - Power Failures (100 ms)
  A (400 Hz) - Power Failures (100 ms)
  A (600 Hz) - Power Failures (100 ms)
  A (800 Hz) - Power Failures (100 ms)
  B (360 Hz) - Power Failures (500 ms)
  B (400 Hz) - Power Failures (500 ms)
  B (600 Hz) - Power Failures (500 ms)
  B (800 Hz) - Power Failures (500 ms)
  C (360 Hz) - Power Failures (3000 ms)
  C (400 Hz) - Power Failures (3000 ms)
  C (600 Hz) - Power Failures (3000 ms)
  C (800 Hz) - Power Failures (3000 ms)
  D (360 Hz) - Power Failures (7000 ms)
  D (400 Hz) - Power Failures (7000 ms)
  D (600 Hz) - Power Failures (7000 ms)
  D (800 Hz) - Power Failures (7000 ms)
 SVF603 Correct Phase Configuration (800 Hz)
  Phase Reversal (360 Hz)
  Phase Reversal (400 Hz)
  Phase Reversal (600 Hz)
 SXF101 Load Measurements - 115 V, 60Hz
 SXF102 A - 115 V, 60Hz
  B - 115 V, 59.5Hz
  C - 115 V, 60.5Hz
  D - 105 V, 60Hz
  E - 105 V, 59.5Hz
  F - 105 V, 60.5Hz
  G - 125 V, 60Hz
  H - 125 V, 59.5Hz
  I - 125 V, 60.5Hz
 SXF105 A (60 Hz) - 0.1Hz per second
  B (60 Hz) - 0.5Hz per second
  C (60 Hz) - 4Hz per second
  D (60 Hz) - 25Hz per second
  E (60 Hz) - 15Hz per second
 SXF106 (Ripple) A (60 Hz) - 1000 mVrms with 50 Hz Voltage Distortion
  B (60 Hz) - 3162 mVrms with 150 Hz Voltage Distortion
  C (60 Hz) - 3162 mVrms with 450 Hz Voltage Distortion
  D (60 Hz) - 1333 mVrms with 1 kHz Voltage Distortion
  E (60 Hz) - 473 mVrms with 3 kHz Voltage Distortion
  F (60 Hz) - 282 mVrms with 5 kHz Voltage Distortion
  G (60 Hz) - 150 mVrms with 10 kHz Voltage Distortion
 SXF108 A (60 Hz) - 115 Vrms with +100 mV DC offset
  B (60 Hz) - 115 Vrms with -100 mV DC offset
 SXF109 A (60 Hz) - Overvoltage Transients (152 Vrms)
  B (60 Hz) - Overvoltage Transients (130 Vrms)
  C (60 Hz) - Overvoltage Transients (130 Vrms)
  D (60 Hz) - Overvoltage Transients x3 (130 Vrms)
  E (60 Hz) - Undervoltage Transients (70 Vrms)
  F (60 Hz) - Undervoltage Transients (70 Vrms)
  G (60 Hz) - Undervoltage Transients (70 Vrms)
  H (60 Hz) - Undervoltage Transients x3 (70 Vrms)
  I (60 Hz) - Combined Transients (70-130 Vrms)
  Repetitive Normal Voltage Transients (100-128 Vrms)
 SXF110 A - Overfrequency Transients (61 Hz)
  B - Overfrequency Transients (61 Hz)
  C - Underfrequency Transients (59 Hz)
  D - Underfrequency Transients (59 Hz)
  E - Combined Frequency Transients (59-61 Hz)
 SXF201 A (60 Hz) - Transfer Interrupt - Nominal Voltage (50 ms)
  B (60 Hz) - Transfer Interrupt - NLSS Voltage (50 ms)
  C (60 Hz) - Transfer Interrupt - NHSS Voltage (50 ms)
  D (60 Hz) - Transfer Interrupt - Nominal Voltage (30 ms)
  E (60 Hz) - Transfer Interrupt - NLSS Voltage (30 ms)
  F (60 Hz) - Transfer Interrupt - NHSS Voltage (30 ms)
  G (60 Hz) - Transfer Interrupt - Nominal Voltage (10 ms)
  H (60 Hz) - Transfer Interrupt - NLSS Voltage (10 ms)
  I (60 Hz) - Transfer Interrupt - NHSS Voltage (10 ms)
  J (60 Hz) - Transfer Interrupt x3 - Nominal Voltage
  K (60 Hz) - Transfer Interrupt - Overvoltage
  L (60 Hz) - Transfer Interrupt - Undervoltage
 SXF301 A - Abnormal Steady State Limits (115 Vrms, 59,5 Hz)
  B - Abnormal Steady State Limits (115 Vrms, 60,5 Hz)
  C - Abnormal Steady State Limits (100 Vrms, 60 Hz)
  D - Abnormal Steady State Limits (100 Vrms, 59,5 Hz)
  E - Abnormal Steady State Limits (100 Vrms, 60,5 Hz)
  F - Abnormal Steady State Limits (128 Vrms, 60 Hz)
  G - Abnormal Steady State Limits (128 Vrms, 59,5 Hz)
  H - Abnormal Steady State Limits (128 Vrms, 60,5 Hz)
 SXF302 A (60 Hz) - Overvoltage Transients (180 Vrms)
  B (60 Hz) - Overvoltage Transients (180 Vrms)
  C (60 Hz) - Overvoltage Transients (160 Vrms)
  D (60 Hz) - Overvoltage Transients (160 Vrms)
  E (60 Hz) - Overvoltage Transients x3 (180 Vrms)
  F (60 Hz) - Undervoltage Transients (50 Vrms)
  G (60 Hz) - Undervoltage Transients (50 Vrms)
  H (60 Hz) - Undervoltage Transients (70 Vrms)
  I (60 Hz) - Undervoltage Transients (70 Vrms)
  J (60 Hz) - Undervoltage Transients x3 (50 Vrms)
  K (60 Hz) - Combined Transients (50-180 Vrms)
 SXF303 A (60 Hz) - Overfrequency Transients (61 Hz)
  B (60 Hz) - Overfrequency Transients (61 Hz)
  C (60 Hz) - Underfrequency Transients (50 Hz)
  D (60 Hz) - Underfrequency Transients (50 Hz)
  E (60 Hz) - Combined Frequency Transients (50-61 Hz)
 SXF401 A - 115 V, 60HzA - 115 V, 60Hz
  B - 115 V, 59.5Hz
  C - 115 V, 60.5Hz
  D - 105 V, 60Hz
  E - 105 V, 59.5Hz
  F - 105 V, 60.5Hz
  G - 125 V, 60Hz
  H - 125 V, 59.5Hz
  I - 125 V, 60.5Hz
 SXF601 A (60 Hz) - Power Failures (100 ms)
  B (60 Hz) - Power Failures (500 ms)
  C (60 Hz) - Power Failures (2000 ms) 
 SXF603 Correct Phase Connection (60 Hz)
  Phase Reversal (60 Hz)