RLY Amplifiers
Robust Amplifiers for Relay Testing
AE Techron’s Relay Testing amplifiers were created to meet the demanding requirements of the power utility industry. With models capable of outputting up to 200 amperes peak current, these Relay Testing amplifiers are powerful enough to put protection relays, fuses and other critical components through a full range of tests.
All models are capable of a controlled-current bandwidth of DC – 10 kHz and a controlled-voltage bandwidth of DC – 100 kHz. Low noise floor, low distortion and minimal phase error make these amplifiers ideal for power grid modeling.
Performance
7212 Output (Voltage Mode) | ||||||||||||
Load | PEAK OUTPUT | RMS OUTPUT | ||||||||||
40mSec Pulse, 30% Duty Cycle |
5 Min, 100% Duty Cycle |
1 Hr, 100% Duty Cycle |
5 Min, 100% Duty Cycle |
1 Hr, 100% Duty Cycle |
||||||||
Volts | Amps | Volts | Amps | Volts | Amps | Volts | Amps | Volts | Amps | Watts | ||
High-Voltage Mode | 32Ω | 166 | 5.1 | 161 | 5 | 161 | 5 | 113 | 3.6 | 113 | 3.6 | 407 |
Mid-Level Mode | 4Ω | 62 | 14.8 | 60 | 14.8 | 59 | 14.6 | 42 | 10.5 | 42 | 10.3 | 432 |
High-Current Mode | 1Ω | 24 | 22.6 | 24 | 22.6 | 24 | 22.6 | 17 | 16 | 17 | 16 | 272 |
Pulse/Burst Output (Current Mode) |
|||||||
Total Load |
60 Hz Sine | DC | |||||
5 minutes | 20 seconds | 0.2 seconds | 5 minutes | 20 seconds | 0.2 seconds | ||
7224RLY | 1.0Ω | 28ARMS / 40Ap | 30ARMS / 43Ap | 33ARMS / 47Ap | 20Ap | 20Ap | 30Ap |
20 seconds | 0.5 seconds | 0.2 seconds | 20 seconds | 0.5 seconds | 0.2 seconds | ||
7548RLY | 0.5Ω | 57ARMS / 80.6Ap | 66ARMS / 93Ap | 66ARMS / 93Ap | 25Ap | 70Ap | 70Ap |
1 minute | 0.5 seconds | 0.2 seconds | 1 minute | 0.5 seconds | 0.2 seconds | ||
7796RLY | 0.19Ω | 125ARMS / 176Ap | 141ARMS / 200Ap | 141ARMS / 200Ap | 60Ap | 188Ap | 188Ap |
0.53Ω | 91ARMS / 128Ap | 137ARMS / 193Ap | 139ARMS / 196Ap | 100Ap | 164Ap | 164Ap | |
1.07Ω | 75ARMS / 107Ap | 83ARMS / 118Ap | 85ARMS / 120Ap | 66Ap | 108Ap | 108Ap |
7212
Up to 113 V RMS, Potential at up to 4A
For Power Grid Simulation
The 7212 is a four-quadrant, 0.44 kVA, DC-enabled power amplifier that was created to meet the exacting requirements of the power utility industry. It features a DC to 250 kHz bandwidth, low noise floor, fast slew rate and a 113V RMS potential. The 7212 can be combined to form a 3-phase Y voltage source, and has a wide range of field-configurable options.
7224RLY
Up to 50 Ap Current Source
For Protection Relay Production Testing and Commissioning
The 7224RLYwas created to meet the demanding requirements of the power utility industry. Capable of outputting a 40 mSec pulse with up to 52 amperes peak current, the 7224RLY is powerful enough to put protection relays, fuses and other critical components through a full range of tests.
7548RLY
Up to 100 Ap Current Source
For Protection Relay Production Testing and Commissioning
The 7548RLYwas created to meet the demanding requirements of the power utility industry. Capable of outputting up to 100 amperes peak current, the 7548RLY is powerful enough to put protection relays, fuses and other critical components through a full range of tests.
7796RLY
Up to 200 Ap Current Source
For Protection Relay Production Testing and Commissioning